Equipment grounding conductor by circuit rating
| Overcurrent device | Copper ground | Aluminum ground | Circuits that read this row |
|---|---|---|---|
| 15 A | 14 AWG | 12 AWG | 15 A |
| 20 A | 12 AWG | 10 AWG | 20 A |
| 60 A | 10 AWG | 8 AWG | 30–60 A |
| 100 A | 8 AWG | 6 AWG | 70–100 A |
| 200 A | 6 AWG | 4 AWG | 125–200 A |
| 300 A | 4 AWG | 2 AWG | 225–300 A |
| 400 A | 3 AWG | 1 AWG | 350–400 A |
The table prints no 30 A, 40 A, 50 A, 70 A, 80 A, 125 A, 150 A, 225 A, or 350 A row. Those ratings take the row above them, which is why a 50 A range circuit and a 30 A dryer circuit both carry a 10 AWG copper ground.
What the equipment ground does
The equipment grounding conductor gives fault current a low-impedance path back to the source, so the overcurrent device opens. Table 250.122 sizes it to carry that current until the device clears. It does not carry the load, which is why it is smaller than the phase conductors on most circuits, and why 250.122(B) only enlarges it when the phase conductors grow beyond what the rating requires.
Circular mils by conductor size
250.122(B) is written in circular mils, so the proportion is computed from the areas rather than from the trade sizes. These values are from Chapter 9 Table 8.
| Size | Circular mils | Size | Circular mils |
|---|---|---|---|
| 14 AWG | 4,110 | 12 AWG | 6,530 |
| 10 AWG | 10,380 | 8 AWG | 16,510 |
| 6 AWG | 26,240 | 4 AWG | 41,740 |
| 3 AWG | 52,620 | 2 AWG | 66,360 |
| 1 AWG | 83,690 | 1/0 AWG | 105,600 |
| 2/0 AWG | 133,100 | 3/0 AWG | 167,800 |
| 4/0 AWG | 211,600 | 250 kcmil | 250,000 |
| 300 kcmil | 300,000 | 350 kcmil | 350,000 |
| 400 kcmil | 400,000 | 500 kcmil | 500,000 |
A kcmil size is its own circular mil count, so 250 kcmil is 250,000. Copper, aluminum, and copper-clad aluminum share the same areas; only the resistance and the ampacity differ.
When the raceway is the ground
250.118 permits metal raceways and the armor of listed cable to serve as the equipment grounding conductor, so a circuit in rigid metal conduit, intermediate metal conduit, or electrical metallic tubing carries no separate ground wire. Where a wire-type grounding conductor runs with the circuit, Table 250.122 sizes it.
Rules behind the table
- The ground is never required to be larger than the circuit conductors it runs with (250.122(A)). It is often smaller, and that is intended.
- Where the ungrounded conductors are increased for any reason other than 310.15(B) or (C) adjustment or correction, the ground is increased in the same proportion by circular mil area (250.122(B)). Longer runs at the same current are the usual cause.
- A service needs a grounding electrode conductor instead, sized from the largest ungrounded service conductor by Table 250.66. That is a different conductor from the equipment ground on a branch circuit, even when both are called "the ground wire".
- Aluminum equipment grounding conductors are permitted where the terminations are listed for aluminum; 250.64(A) restricts aluminum within 18 in. of the earth for the grounding electrode conductor, not for the equipment ground.