Equipment grounding conductor by circuit rating

Minimum size equipment grounding conductors, NEC 2023 Table 250.122. Rows are printed against the rating of the overcurrent device, so a circuit reads the first row at or above its own rating.
Overcurrent deviceCopper groundAluminum groundCircuits that read this row
15 A14 AWG12 AWG15 A
20 A12 AWG10 AWG20 A
60 A10 AWG8 AWG30–60 A
100 A8 AWG6 AWG70–100 A
200 A6 AWG4 AWG125–200 A
300 A4 AWG2 AWG225–300 A
400 A3 AWG1 AWG350–400 A

The table prints no 30 A, 40 A, 50 A, 70 A, 80 A, 125 A, 150 A, 225 A, or 350 A row. Those ratings take the row above them, which is why a 50 A range circuit and a 30 A dryer circuit both carry a 10 AWG copper ground.

What the equipment ground does

The equipment grounding conductor gives fault current a low-impedance path back to the source, so the overcurrent device opens. Table 250.122 sizes it to carry that current until the device clears. It does not carry the load, which is why it is smaller than the phase conductors on most circuits, and why 250.122(B) only enlarges it when the phase conductors grow beyond what the rating requires.

Circular mils by conductor size

250.122(B) is written in circular mils, so the proportion is computed from the areas rather than from the trade sizes. These values are from Chapter 9 Table 8.

Circular mils for the conductor sizes in Tables 250.122 and 250.66. NEC 2023 Chapter 9 Table 8.
SizeCircular milsSizeCircular mils
14 AWG4,11012 AWG6,530
10 AWG10,3808 AWG16,510
6 AWG26,2404 AWG41,740
3 AWG52,6202 AWG66,360
1 AWG83,6901/0 AWG105,600
2/0 AWG133,1003/0 AWG167,800
4/0 AWG211,600250 kcmil250,000
300 kcmil300,000350 kcmil350,000
400 kcmil400,000500 kcmil500,000

A kcmil size is its own circular mil count, so 250 kcmil is 250,000. Copper, aluminum, and copper-clad aluminum share the same areas; only the resistance and the ampacity differ.

When the raceway is the ground

250.118 permits metal raceways and the armor of listed cable to serve as the equipment grounding conductor, so a circuit in rigid metal conduit, intermediate metal conduit, or electrical metallic tubing carries no separate ground wire. Where a wire-type grounding conductor runs with the circuit, Table 250.122 sizes it.

Rules behind the table

  • The ground is never required to be larger than the circuit conductors it runs with (250.122(A)). It is often smaller, and that is intended.
  • Where the ungrounded conductors are increased for any reason other than 310.15(B) or (C) adjustment or correction, the ground is increased in the same proportion by circular mil area (250.122(B)). Longer runs at the same current are the usual cause.
  • A service needs a grounding electrode conductor instead, sized from the largest ungrounded service conductor by Table 250.66. That is a different conductor from the equipment ground on a branch circuit, even when both are called "the ground wire".
  • Aluminum equipment grounding conductors are permitted where the terminations are listed for aluminum; 250.64(A) restricts aluminum within 18 in. of the earth for the grounding electrode conductor, not for the equipment ground.