Equipment grounding conductor
| Overcurrent device | Copper | Aluminum |
|---|---|---|
| 20 A | 12 AWG | 10 AWG |
This row serves the 20 A branch circuit on its own. A 12 AWG copper ground matches the ungrounded conductor that 240.4(D) pairs with a 20 A breaker, so the two smallest rows look automatic. The sizes part company at 60 A.
The usual slip is keeping the ground at 14 AWG on a 20 A circuit because the two wires look alike. The 20 A row prints 12 AWG copper. 250.122(A) does not help here: it caps the ground at the circuit conductors, it does not license a smaller one.
When the ground has to be increased
The table sizes the ground from the overcurrent device, so it assumes the phase conductors are the smallest ones that carry the rating. Enlarge them for any reason other than the adjustment or correction in 310.15(B) or (C) and 250.122(B) applies. The ground grows in the same proportion by circular mil area, rounded up to a listed size.
| Phase conductor | Circular mils | Copper ground | Aluminum ground |
|---|---|---|---|
| 12 AWG | 6,530 (1.00×) | 12 AWG | 12 AWG |
| 10 AWG | 10,380 (1.59×) | 10 AWG | 10 AWG |
| 8 AWG | 16,510 (2.53×) | 8 AWG | 8 AWG |
| 6 AWG | 26,240 (4.02×) | 6 AWG | 6 AWG |
12 AWG copper reaches 90 ft at 3% drop on a 240 V single-phase circuit. One size past the minimum, 12 AWG to 10 AWG, takes the ground from 12 AWG to 10 AWG.
The result is still capped by 250.122(A) at the ungrounded conductors it runs with. The wire size for a 20 A circuit comes from that table.
20 A ground wire questions
What size ground wire for a 20 A circuit?
12 AWG copper or 10 AWG aluminum. Table 250.122 prints rows against the overcurrent device rating, so a 20 A circuit reads the 20 A row and takes the size printed there. The equipment grounding conductor runs with the circuit conductors and bonds the raceway and equipment. It is not the grounding electrode conductor that 250.66 covers.
Does the ground wire have to be the same size as the circuit conductors?
No. Table 250.122 sizes the equipment grounding conductor by the overcurrent device rating, and 250.122(A) only requires that it never be larger than the ungrounded conductors. On small circuits the two sizes often agree. On feeders they usually do not.
When does the ground wire have to get bigger?
250.122(B) requires the equipment grounding conductor to be increased in the same proportion by circular mil area whenever the ungrounded conductors are increased for any reason other than the adjustment or correction required by 310.15(B) or (C). Upsizing a long run for voltage drop is the case that catches people: the phase conductors get larger, the ground stays at the table size, and the installation is wrong.
Can the equipment grounding conductor be aluminum?
Table 250.122 prints an aluminum and copper-clad aluminum column, so yes, where the terminations are listed for aluminum and 110.14 is followed. The restriction in 250.64(A) on aluminum within 18 in. of the earth applies to the grounding electrode conductor, not to the equipment grounding conductor in a circuit.
What ground does a 20 A circuit need if I upsize for voltage drop?
10 AWG copper, or 10 AWG aluminum. 250.122(B) scales the ground with the circular mils, so moving from 12 AWG to 10 AWG takes the copper ground from 12 AWG to 10 AWG. The table above does the same arithmetic for every larger phase conductor.
Is a larger ground wire a problem?
No. Table 250.122 is a minimum, and 250.122(A) says the equipment grounding conductor is never required to be larger than the ungrounded conductors it runs with. A larger ground still has to land on terminals listed for the size, which is the practical limit.