Equipment grounding conductor

Minimum size equipment grounding conductor for a 300 A overcurrent device. NEC 2023 Table 250.122. The aluminum column covers aluminum and copper-clad aluminum.
Overcurrent deviceCopperAluminum
300 A4 AWG2 AWG

This row covers 225 A and 300 A. A 225 A panel is uncommon in a dwelling and ordinary in light commercial work, and it reads the same 4 AWG copper ground as a 300 A circuit.

A 225 A panel reads this row, and a larger ground is permitted there: Table 250.122 is a minimum, and 250.122(A) still caps it at the ungrounded conductors.

Which circuits read the 300 A row

Table 250.122 prints a row at 300 A and then skips ahead, so a 225 A circuit takes this row as well. The size does not change across those ratings: it stays at 4 AWG copper or 2 AWG aluminum.

Sizing the ground from the breaker rating, rather than from the conductor, is the point of the table. A 225 A circuit whose conductors are upsized for voltage drop still starts from the 300 A row; 250.122(B) then raises the ground in proportion to the increase in circular mil area.

When the ground has to be increased

The table sizes the ground from the overcurrent device, so it assumes the phase conductors are the smallest ones that carry the rating. Enlarge them for any reason other than the adjustment or correction in 310.15(B) or (C) and 250.122(B) applies. The ground grows in the same proportion by circular mil area, rounded up to a listed size.

Copper phase conductors from the minimum for a 300 A circuit upward, and the ground 250.122(B) requires at each one. The first row is the Table 250.122 answer.
Phase conductorCircular milsCopper groundAluminum ground
350 kcmil350,000 (1.00×)4 AWG2 AWG
400 kcmil400,000 (1.14×)3 AWG1 AWG
500 kcmil500,000 (1.43×)2 AWG1/0 AWG
600 kcmil600,000 (1.71×)1 AWG2/0 AWG

350 kcmil copper reaches 325 ft at 3% drop on a 240 V single-phase circuit. One size past the minimum, 350 kcmil to 400 kcmil, takes the ground from 4 AWG to 3 AWG.

The result is still capped by 250.122(A) at the ungrounded conductors it runs with. The 300 A wire size works out from Table 310.16 the same way.

If you meant the service grounding electrode conductor

A service or a feeder from a service needs a grounding electrode conductor, and Table 250.66 sizes it from the largest ungrounded service conductor, not from the breaker rating. Both are called the ground wire, which is where the confusion starts. Table 250.66 is printed here in full.

Grounding electrode conductor for alternating-current systems. NEC 2023 Table 250.66.
Copper service conductorAluminum service conductorCopper GECAluminum GEC
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 or 1/0 AWG2/0 or 3/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
over 3/0 through 350 kcmilover 250 through 500 kcmil2 AWG1/0 AWG
over 350 through 600 kcmilover 500 through 900 kcmil1/0 AWG3/0 AWG
over 600 through 1100 kcmilover 900 through 1750 kcmil2/0 AWG4/0 AWG
over 1100 kcmilover 1750 kcmil3/0 AWG250 kcmil

Three caps override the table for a single electrode: 6 AWG copper is the largest a rod, pipe, or plate connection needs (250.66(A)), 4 AWG copper for a concrete-encased electrode (250.66(B)), and 2 AWG copper for a ground ring (250.66(C)). Aluminum is barred within 18 in. of the earth by 250.64(A).

300 A ground wire questions

What size ground wire for a 300 A circuit?

4 AWG copper or 2 AWG aluminum. Table 250.122 prints rows against the overcurrent device rating, so a 300 A circuit reads the 300 A row and takes the size printed there. The equipment grounding conductor runs with the circuit conductors and bonds the raceway and equipment. It is not the grounding electrode conductor that 250.66 covers.

Why is there no 225 A row in Table 250.122?

Because the table jumps from the 200 A row to the 300 A row. A 225 A circuit takes the first row at or above its rating, which is the 300 A row, so it takes 4 AWG copper or 2 AWG aluminum.

Does the ground wire have to be the same size as the circuit conductors?

No. Table 250.122 sizes the equipment grounding conductor by the overcurrent device rating, and 250.122(A) only requires that it never be larger than the ungrounded conductors. On small circuits the two sizes often agree. On feeders they usually do not.

When does the ground wire have to get bigger?

250.122(B) requires the equipment grounding conductor to be increased in the same proportion by circular mil area whenever the ungrounded conductors are increased for any reason other than the adjustment or correction required by 310.15(B) or (C). Upsizing a long run for voltage drop is the case that catches people: the phase conductors get larger, the ground stays at the table size, and the installation is wrong.

Can the equipment grounding conductor be aluminum?

Table 250.122 prints an aluminum and copper-clad aluminum column, so yes, where the terminations are listed for aluminum and 110.14 is followed. The restriction in 250.64(A) on aluminum within 18 in. of the earth applies to the grounding electrode conductor, not to the equipment grounding conductor in a circuit.

What ground does a 300 A circuit need if I upsize for voltage drop?

3 AWG copper, or 1 AWG aluminum. 250.122(B) scales the ground with the circular mils, so moving from 350 kcmil to 400 kcmil takes the copper ground from 4 AWG to 3 AWG. The table above does the same arithmetic for every larger phase conductor.

Is a larger ground wire a problem?

No. Table 250.122 is a minimum, and 250.122(A) says the equipment grounding conductor is never required to be larger than the ungrounded conductors it runs with. A larger ground still has to land on terminals listed for the size, which is the practical limit.