01. Table 310.16

Selected ampacity
14 AWG Copper @60°C → 15A

NEC 240.4(D)Small-conductor overcurrent protection is limited to 15A. Apply this maximum protective limit after any ambient correction or conductor-count adjustment factors.

Residential branch circuits typically require the 60°C column per NEC 110.14(C). Use the 75°C column only when all equipment terminals and connectors are rated for 75°C or higher.

NEC Table 310.16 (2023). Copper. Not more than three current-carrying conductors. 30°C, 86°F ambient.
Size60°CTW, UF75°CRHW, THHW, THW, THWN, XHHW, USE, ZW90°CTBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2Max overcurrent protection under NEC 240.4(D). An em dash means see 240.4.240.4(D)
7A
10A
15A
20A
30A
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4
not listed in 240.4(D), see 240.4

Max represents the maximum overcurrent protection rating from NEC 240.4(D) for small conductors. — indicates the size is not subject to a specific 240.4(D) cap. Refer to NEC 240.4 for general overcurrent protection rules.

Insulation types correspond to NEC Table 310.16 column classifications: Copper 60°C: TW, UF. 75°C: RHW, THHW, THW, THWN, XHHW, USE, ZW. Copper 90°C: TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2. Aluminum 60°C: TW, UF. 75°C: RHW, THHW, THW, THWN, XHHW, USE. Aluminum 90°C: TBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2.

02. Copper and aluminum

Complete wire ampacity chart

Complete ampacity ratings from NEC Table 310.16 (2023) for copper and aluminum or copper-clad aluminum conductors. A hyphen indicates the table lists no rating for that size and temperature combination.

Ampacity chart. NEC Table 310.16, 30°C ambient, not more than three current-carrying conductors.
SizeCu60°CTW, UFCu75°CRHW, THHW, THW, THWN, XHHW, USE, ZWCu90°CTBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2Al60°CTW, UFAl75°CRHW, THHW, THW, THWN, XHHW, USEAl90°CTBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2
18AWG--14---
16AWG--18---
14AWG152025---
12AWG202530152025
10AWG303540253035
8AWG405055354045
6AWG556575405055
4AWG708595556575
3AWG85100115657585
2AWG951151307590100
1AWG11013014585100115
1/0AWG125150170100120135
2/0AWG145175195115135150
3/0AWG165200225130155175
4/0AWG195230260150180205
250kcmil215255290170205230
300kcmil240285320195230260
350kcmil260310350210250280
400kcmil280335380225270305
500kcmil320380430260310350
600kcmil350420475285340385
700kcmil385460520315375425
750kcmil400475535320385435
800kcmil410490555330395445
900kcmil435520585355425480
1000kcmil455545615375445500
1250kcmil495590665405485545
1500kcmil525625705435520585
1750kcmil545650735455545615
2000kcmil555665750470560630
Copper. NEC Table 310.16, 30°C ambient, not more than three current-carrying conductors.
SizeCu60°CTW, UFCu75°CRHW, THHW, THW, THWN, XHHW, USE, ZWCu90°CTBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2
18AWG--14
16AWG--18
14AWG152025
12AWG202530
10AWG303540
8AWG405055
6AWG556575
4AWG708595
3AWG85100115
2AWG95115130
1AWG110130145
1/0AWG125150170
2/0AWG145175195
3/0AWG165200225
4/0AWG195230260
250kcmil215255290
300kcmil240285320
350kcmil260310350
400kcmil280335380
500kcmil320380430
600kcmil350420475
700kcmil385460520
750kcmil400475535
800kcmil410490555
900kcmil435520585
1000kcmil455545615
1250kcmil495590665
1500kcmil525625705
1750kcmil545650735
2000kcmil555665750
Aluminum or copper-clad aluminum. NEC Table 310.16, 30°C ambient, not more than three current-carrying conductors.
SizeAl60°CTW, UFAl75°CRHW, THHW, THW, THWN, XHHW, USEAl90°CTBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2
12AWG152025
10AWG253035
8AWG354045
6AWG405055
4AWG556575
3AWG657585
2AWG7590100
1AWG85100115
1/0AWG100120135
2/0AWG115135150
3/0AWG130155175
4/0AWG150180205
250kcmil170205230
300kcmil195230260
350kcmil210250280
400kcmil225270305
500kcmil260310350
600kcmil285340385
700kcmil315375425
750kcmil320385435
800kcmil330395445
900kcmil355425480
1000kcmil375445500
1250kcmil405485545
1500kcmil435520585
1750kcmil455545615
2000kcmil470560630

Insulation types correspond to NEC Table 310.16 column classifications: Copper 60°C: TW, UF. 75°C: RHW, THHW, THW, THWN, XHHW, USE, ZW. Copper 90°C: TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2. Aluminum 60°C: TW, UF. 75°C: RHW, THHW, THW, THWN, XHHW, USE. Aluminum 90°C: TBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2.

03. Downloads

Download the wire ampacity chart

High-resolution PNG reference charts and a printable PDF document, generated directly from the official NEC 2023 Table 310.16 values.

Wire ampacity chart for copper and aluminum conductors, NEC Table 310.16 (2023), 60°C, 75°C, and 90°C
Complete copper and aluminum ampacity chart, NEC Table 310.16 (2023).
Wire ampacity chart for common sizes 14 AWG through 4/0 copper and aluminum, NEC 310.16
Common residential and commercial sizes (14 AWG through 4/0).

04. Ambient correction

Ambient temperature correction

Correction factors from NEC Table 310.15(B)(1) based on a 30°C (86°F) ambient temperature. Multiply the Table 310.16 ampacity by the factor corresponding to the conductor's insulation temperature rating.

Ambient temperature correction factors from NEC 310.15(B)(1)
Ambient °CAmbient °F60°C75°C90°C
10 or less50 or less1.291.201.15
11–1551–591.221.151.12
16–2060–681.151.111.08
21–2569–771.081.051.04
26–3078–861.001.001.00
31–3587–950.910.940.96
36–4096–1040.820.880.91
41–45105–1130.710.820.87
46–50114–1220.580.750.82
51–55123–1310.410.670.76
56–60132–140-0.580.71
61–65141–149-0.470.65
66–70150–158-0.330.58
71–75159–167--0.50
76–80168–176--0.41
81–85177–185--0.29

05. More than three conductors

More than three current-carrying conductors

Adjustment factors from NEC Table 310.15(C)(1). Apply the derating percentage to the Table 310.16 ampacity after applying any ambient temperature correction.

Adjustment factors for more than three current-carrying conductors from NEC 310.15(C)(1)
Number of conductorsPercent of Table 310.16
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

06. Questions

Ampacity chart questions

What is an ampacity chart?
An ampacity chart specifies the maximum current, in amperes, that a conductor can carry continuously under specific operating conditions without exceeding its insulation temperature rating. This chart is based on NEC Table 310.16 (2023), which applies to not more than three current-carrying conductors installed in a raceway, cable, or direct burial in earth, at a design ambient temperature of 30°C (86°F).
Why is 14 AWG copper limited to a 15 A breaker?
While NEC Table 310.16 lists the allowable ampacity for 14 AWG copper as 15 A at 60°C, 20 A at 75°C, and 25 A at 90°C, NEC 240.4(D)(3) mandates that overcurrent protection for small conductors must not exceed 15 A. Similar limits apply to 12 AWG copper (20 A) and 10 AWG copper (30 A), unless explicitly permitted under 240.4(E) or (G). Therefore, you cannot size the circuit breaker purely from the 75°C or 90°C columns.
When can I use the 75°C column instead of 60°C?
Standard residential branch circuits typically require sizing from the 60°C column per NEC 110.14(C). The 75°C column may only be utilized when both the conductor insulation and all connected equipment terminals, breakers, and devices are explicitly rated for 75°C or higher. Even when using a conductor with 90°C insulation landed on 75°C terminals, the ampacity must be determined from the 75°C column, as the lowest-rated element in the circuit governs the allowable capacity.
How do I apply ambient temperature correction?
Table 310.16 base values assume an ambient temperature of 30°C (86°F). If conductors operate in an environment with higher or lower ambient temperatures, you must multiply the table ampacity by the appropriate correction factor from NEC Table 310.15(B)(1) for the conductor's temperature rating. Any small-conductor limits under NEC 240.4(D) are enforced after all correction factors have been applied.
What if there are more than three current-carrying conductors?
Per NEC 310.15(C)(1), when more than three current-carrying conductors are installed in the same raceway or cable, an adjustment (derating) factor must be applied to prevent overheating: 4 to 6 conductors require an 80% multiplier, while 7 to 9 conductors require 70%. Consult the conductor count adjustment table on this page for higher counts. When counting conductors, do not include equipment grounding conductors, or neutral conductors that carry only unbalanced currents in 3-wire or 4-wire systems.